Show Info
Date: 2014/8/27-2014/8/30
Venue:
Taipei World Trade Center NanGang Exhibition Hall 4F
Organizer:
Chan Chao International Co., Ltd.
Economic Daily
Featured Suppliers
- KUKA AUTOMATION TAIWAN LTD. Booth No : M108
- TBI MOTION TECHNOLOGY CO., LTD. Booth No : M735
eYc THS88MAX Industrial High Pressure Dew Point Transmitter
Modeeel: eYc THS88MAX
Industry: Automatic/Industrial Machines & Equipments / Testing Equipment / Inspecting/Measuring Instrument and Parts
Supplier; YUDEN-TECH CO.,LTD.
Booth No: M530
Characteristics
-Features
Dew point calibration, highly accuracy, 4 ... 20 mA and RS-485 output
Reduce insensitivity temperature zone, quickly response
Hysteresis compensation, resistance to moisture, extreme high and low humidity impact
EMC anti-interference, anti-condensation, low-temperature influence, long-term stability
Three thread (1/2″PT, 1/2″G, and 5/8″UNF) mode can be selected
Applications
Compressed air system / Air separation equipment / Freezer / Adsorption machine / Plastic dryer / Industrial drying process / Paper / Chemical process monitoring
Specifications
Input
Input type:Capacitive humidity sensor & Pt100
Operating range of dew point:-60 ... +60 dp°C
Output
Max. scaling range:Dew point:-100 ... +60 dp°C
Dew point switch to another physical quantity range:Frost point:-60 ... 0 fp°C, Absolute humid.(Volume)0 ... 50000 ppm/v, Absolute humid.(Weight)0 ... 50000 ppm/w
Output signal:Standard 4 ... 20 mA+RS-485 / 0 ... 10 V+RS-485 on request
Signal connection:3-wire
Linear accuracy:±1 dp°C (at -20 ... +20 dp°C) / ±1.5 dp°C(at -40 ... +20 dp°C) / ±2 dp°C (at -60 dp°C) / Reference (at -100 ... -60 dp°C)
Load resistance:Current output:≦ 500 Ω / Voltage output:≧ 100 KΩ
Output calibration(ZERO & SPAN)adjustment range:Software
Response time t90(Temp. at+25°C):<20 sec
Electrical
Power supply:DC 24 V±15%
Current consumption:DC 24 V, 50 mA
Electrical connection:M12 connector
Environment
Medium:Air
Operating Temp. for housing:-40 ... +60°C
Operating Humid. for housing:0 ... 95%RH (Non-condensing)
Operating Temp. for probe:-40 ... +60°C
Storage temperature:-25 ... +60°C
Pressure resistance:16 bar
Installation
Installation:1/2″PT, 1/2″G, and 5/8″UNF
Protection
IP rating:IP65(Probe:IP20)
Electrical protection:■ Polarity protection ■ Over-voltage ■ Short-circuit
Material
Housing:S.S.(SUS304)
Probe:S.S.(SUS304);SUS sintered filter(SUS316)
Weight:168 g
Featured products
-
eYc FTE120 OEM Air Velocity Transmitter
-
eYc THS88MAX Industrial High Pressure Dew Point Transmitter
-
eYc PHD330 Industrial Differential Pressure Transmitter
-
eYc AFMT Average Flow Measuring Tube ( Pitot tube )
-
eYc FTM06D Thermal Mass Flow Transmitter
-
eYc THM06 Industrial Temperature and Humidity Transmitter
-
eYc FTM84/85 Industrial Grade High Accuracy Thermal Air Velocity Transmitter
-
eYc FTM94/95 Industrial Grade High Accuracy Thermal Air Velocity Transmitter
-
eYc THM80X Series Industrial High Accuracy Temp. & Humidity Transmitter