Our Products
- Shafts, Couplings, Keys and Clutches (1)
- Other Machinery (1)
- Fabric Embossing Calendering Machines (1)
- Air-conditioning Equipment (1)
Contact Information
3F., No.61, Sec.2, Sihchuan Rd.,Banciao Dist., New Taipei City 220, Taiwan
Tel: 886-2-89669005
Fax: 886-2-89669001
KeyPro Heat Pump Water Heater
Model: KPA-05
Category: Automatic/Industrial Machines & Equipments / Industrial Machines / Air-conditioning Equipment
Characteristics
KeyPro Heat Pump Water Heater provides energy efficient water heating and space heating solutions. It is custom designed, high capacity, to meet commercial and industrial application requirements. By collecting free energy easily from the air, hot water source or geo-thermal, the heat pump water heating systems can generate hot water or space heat with very low carbon emissions and operating costs. The heat pump water heater generates hot water and storage the hot water in tanks available for using constantly.
Principle of Heat Pump Water Heater
Heat Pump Water Heater is driven by very low electricity to collect heat source and release heat to generate hot water by using heat exchanger.
Heat is enlarged with Heat Pump.
Eco-friendly
Heat Pump Water Heater takes advantage of free heat source, and there is no emission to cause air pollution. It can help to reduce carbon emissions, Ozone Depletion and global warming.
Trends
The commercial and industrial heat pump water heater market is growing globally. It is ideal match the eco environment and energy efficient. More and more countries trend to urge their commercial or industrial unit reduces carbon emission. It is right time to install a heat pump water heater.
Cost Effective
The energy costs is rising. With less power consumption, heat pump water heater can also reduce operation costs to help control your budget. The little expense can provide reliable source of hot water.
Advantage:
.Energy Efficient: Compare with other hot water supply systems, Heat Pump's COP rating is 4 times of
electric heating water heater, 3 times of gas water heater, 2 times of oil fired boiler.
.Preheat: Heat pump water heater preheats water for existing hot water supply systems.
.Refrigerant: Heat pump water heater use HFC refrigerant, it does not cause ozone depletion.
.Safety: The operation of the heat pump has no burning and exhaust gas or carbon emission. Compare with
possible explosion of boiler, emission of toxic gas and leakage of electricity, heat pump is safety.
.Multi-function: Heat pump water heater can supply hot water and space heating, also it is available to
serve functions i.e. supply cool air, icy water or air dehumidified, those suggest to design
and work with other facilities.
.Simple to operate: Operate heat pump water heater is easy with its auto control system.
.Experienced technician team work: provide the best solutions and back up for your projects.
Benefits:
. With advanced technology, integration capability and services, our heat pump water heater is weatherproof
durable with excellent quality to provide reliable hot water for many years to come.
. Compare with electric heater or boiler, heat pump water heater can save energy costs up to 70% or more.
Applications:
■ Commercial hot water
■ Space heating
■ Pool heating
■ Preheat water
■ Industrial process hot water
Installation:
■ Commercial facilities and building: Hotel / Resorts / Hospital / School / Government / Military / Pool
Health care center / Restaurant
■ Industrial facilities and building: Preheat water / Sterilizer system / electroplate / Manufacturing facilities
Clean hot water for PCB / Agriculture green house / Mobile
Specifications
HFC Heat Pump Series
Model No. |
KPA-05 |
KPA-10 |
KPA-20 |
KPA-30 |
KPW-05 |
KPW-10 |
KPW-20 |
KPW-30 |
Heat Source |
Air to Water |
Water to Water |
||||||
Heating Capacity (kw) |
16.7 |
25.9 |
51.3 |
78.6 |
16.7 |
25.9 |
51.3 |
78.6 |
Cooling Capacity (kw) |
– |
– |
– |
– |
12.4 |
19.1 |
37.8 |
57.9 |
Hot Water Flow (LPM) |
53 |
76 |
151 |
238 |
53 |
76 |
151 |
238 |
Chilled water Flow (LPM) |
– |
– |
– |
– |
38 |
60 |
110 |
174 |
Outlet Water Temperature |
55°C |
|||||||
Motor of Fan (HP) |
0.5 |
1 |
1x2 |
1x2 |
– |
– |
– |
– |
Power Consumption (kw) |
5.1 |
7.9 |
15.1 |
24.3 |
5.1 |
7.9 |
15.1 |
24.3 |
Refrigerant |
R410A / R134a |
|||||||
Power Supply |
3Ph 220V/380V/440V /50/60Hz |
3Ph 220V/380V/440V /50/60Hz |
||||||
Dimensions WxHxD (m) |
1x0.8x1.5 |
1.2x0.8x1.6 |
1.6x1.1x1.7 |
2.2x1.1x2 |
1x0.8x0.8 |
1.2x1x0.9 |
1.5x1x1 |
1.5x1.2x1 |
Weight (kg) |
275 |
300 |
575 |
610 |
180 |
280 |
410 |
510 |
﹡This specification cannot be reproduced and is subject to change without prior notification.