Our Products
Contact Information
10F., No.123-3, Sing-De Rd., San-Chong Dist., New Taipei City 241, Taiwan
Tel: 886-2-85123185
Fax: 886-2-85123186
Industry Grade On Line UPS - 1 Phase
Model: LUV Series
Category: Automatic/Industrial Machines & Equipments / Industrial Machines / Electrical Power Machinery
Characteristics
# Industry Grade UPS
# Full Bridge & Double Conversion UPS
# With ISO Transformer
# SCR Static Transfer Switch
# DC Start
# Automatic Detect Battery Status
# External Battery Bank (optional)
Specifications
|
Model |
LUV-40 |
LUV-50 |
LUV-60 |
LUV-80 |
LUV-100 |
LUV-150 |
LUV-200 |
|||||||
|
Capacity |
4KVA |
5KVA |
6KVA |
8KVA |
10KVA |
15KVA |
20KVA |
|||||||
|
Input |
Voltage |
90 ~ 149VAC (115VAC) / 180 ~ 280VAC (230VAC) |
||||||||||||
|
Frequency |
50Hz or 60Hz ± 5% |
|||||||||||||
|
Phase |
1P2W+G / 3P3W+G / 3P4W+G |
|||||||||||||
|
Power Factor |
0.8 |
|||||||||||||
|
Output |
Voltage |
115VAC or 230VAC ± 2% |
||||||||||||
|
Phase |
1P2W+G |
|||||||||||||
|
Voltage Regulation |
± 1% at linear load |
|||||||||||||
|
Frequency |
50Hz or 60Hz ± 0.5% |
|||||||||||||
|
Waveform Distortion |
Pure Sine Wave less than 3% at full load |
|||||||||||||
|
Crest Factor |
3:1 |
|||||||||||||
|
Overload Capacity |
100% ~ 124% continuous, >125% for 25 seconds, >135% to bypass |
|||||||||||||
|
Efficiency AC to AC |
>80% at battery fully charge |
|||||||||||||
|
Battery |
Type |
Rechargeable, sealed maintenance free |
||||||||||||
|
Backup Time |
10 minutes at full load and 25 minutes at half load |
|||||||||||||
|
Recharge Time |
4 ~ 8 hours 90% after fully discharge |
|||||||||||||
|
Transfer Time |
Main Inverter |
No break |
||||||||||||
|
Indicator |
LCD Display |
Input/Output & Battery Voltage, Frequency, Output Load, Operation Temperature |
||||||||||||
|
LED Display |
Mimic display |
|||||||||||||
|
Audible Alarm |
Mains Fail |
Sounds every 4 seconds after line fails |
||||||||||||
|
Battery Low |
Sounds every second when approaches battery low level |
|||||||||||||
|
UPS Fault |
Continuous alarm |
|||||||||||||
|
Protection |
Short Circuit |
When a short circuit occurs, the UPS will not transfer to Bypass but emit a sustained tone. Once the short circuit is removed, the tone stops and the whole system operates normally again. The UPS stops supplying power if the period of a short circuit is longer 3 seconds. |
||||||||||||
|
Lightning : Yes Surge : Yes |
||||||||||||||
|
Environment |
Temperature |
0゚C ~ 40゚C |
||||||||||||
|
Humidity |
0% ~ 90%, non-condensing |
|||||||||||||
|
Noise Level |
<50dB at 1 meter |
|||||||||||||
|
Communication |
Interface Port |
RS-232 or DB9 |
||||||||||||
|
Dimension W*H*D(mm) |
UPS |
260*800*660 |
260 900 660 |
310 900 660 |
360*740*870 |
|||||||||
|
Battery Bank |
N/A |
360*740*870 |
||||||||||||
|
Net Weight |
UPS |
120kgs |
130kgs |
160kgs |
190kgs |
320kgs |
190kgs |
230kgs |
||||||
|
Battery bank |
N/A |
200kgs |
200kgs |
|||||||||||
Featured products