Our Products
Contact Information
10F., No.123-3, Sing-De Rd., San-Chong Dist., New Taipei City 241, Taiwan
Tel: 886-2-85123185
Fax: 886-2-85123186
Industry Grade On Line UPS - 3 Phase
Model: LTH Series
Category: Automatic/Industrial Machines & Equipments / Industrial Machines / Electrical Power Machinery
Characteristics
# Full Bridge & Double Conversion Design UPS
# DC Start Capability
# UPS Self Detection
# Advanced Battery Management
# Input True Galvanic Isolation Transformer
# Per Phase with Individual Inverter Support
Specifications
|
Model |
LTH-10 |
LTH-20 |
LTH-30 |
LTH-40 |
LTH-50 |
LTH-60 |
LTH-80 |
LTH-100 |
|
|
Capacity |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
|
|
Input (Rectifier) |
Voltage |
380VAC / 400VAC / 415VAC, 3 Phase 4 Wire |
|||||||
|
Frequency |
50Hz or 60Hz ± 5% |
||||||||
|
Power Walk-in |
0 ~ 100% : 10 seconds |
||||||||
|
Output (Inverter) |
Voltage |
380VAC / 400VAC / 415VAC, 3 Phase 4 Wire |
|||||||
|
Frequency |
50Hz or 60Hz ± 0.5% |
||||||||
|
Static Regulation |
± 1% at linear load |
||||||||
|
Dynamic Regulation |
<=2% at 50% load unbalance, <=5% at 100% load unbalance |
||||||||
|
THD Distortion |
<=3% at linear load, <=5% at non-linear load |
||||||||
|
Transient Response |
<5ms |
||||||||
|
Power Factor |
0.8 |
||||||||
|
Overload Capacity |
100% ~124% for 10 minutes, >125% for 1 minute, >150% to bypass |
||||||||
|
Battery |
Voltage |
192V (12V*16pcs) |
348V (12V*29pcs) |
||||||
|
Max. Charge Current |
5A |
10A |
|||||||
|
Float Voltage |
216V |
392V |
|||||||
|
Boost Voltage |
230V |
420V |
|||||||
|
Recharge Time |
4 ~ 8 hours 90% after fully discharge |
||||||||
|
Static Switch |
Main <-> Inverter |
No break |
|||||||
|
Indicator |
LCD Display |
Input / Output Voltage, Frequency, Output Loading Status, Battery Status, Battery Replacement Warning, Phase Site Wiring Error, Event Log |
|||||||
|
LED Display |
Mimic display |
||||||||
|
Protection |
Output Short |
Yes |
|||||||
|
Lighting/EMI Filter |
Yes |
||||||||
|
Environment |
Temperature |
0゚C ~ 40゚C |
|||||||
|
Humidity |
0% ~ 90%, non-condensing |
||||||||
|
Noise Level |
<60dB at 1 meter |
<65dB at 1 meter |
|||||||
|
Communication |
Interface Port |
RS-232 or DB9, SNMP adaptor (option), RS-485 (option), AS-400(option) |
|||||||
|
Dimension W*H*D(mm) |
UPS |
660*1550*800 |
660*1550*800 |
1110*1710*850 |
|||||
|
Battery Bank |
660*1550*800 |
660*1550*800 |
|||||||
|
Net Weight |
UPS |
500kgs |
600kgs |
650kgs |
700kgs |
600kgs |
700kgs |
900kgs |
1100kgs |
|
Battery bank |
430kgs |
500kgs |
630kgs |
1100kgs |
|||||
Featured products