Our Products
Contact Information
No.33, Ln. 428, Sec. 3, Wenhua Rd., Rende Dist., Tainan City 717, Taiwan
Tel: 886-6-3110008
Fax: 886-6-3110522
IAQ LED Display Monitoring System
Model: JNC- IAQ Color System
Category: Automatic/Industrial Machines & Equipments / Industrial Machines / Industrial Instruments & Equipment
Characteristics
1. With Web server interface and Wi-Fi
2. The Chinese interface is easy for operation and without manual
3. It can show IAQ value and welcome words or a government decree simultaneously
4. The IAQ LED display monitoring has long service life and high speedy value update
5. The program interface has prompt full-color display. It show full-color display state on program interface
6. With data record/ Real Time/ Historical trend chart (LAN program)
7. Printing trend chart and transfer to data report (LAN program)
8. Calibration interface with date and time
9. Calibration interface of IAQ sensor
10.Optional: TVOC, CO, O3, PM2.5, PM10, HCHO Sensor
11.Setting of sensor: name/ unit/ range/ alarm/ delay time/ offset/ gain
12.Limitless of link CTR230 and CTR100
13.Setting to search CTR100 or CTR230: IP/Name, Location Form
14.In the IP address that with external internet to browsing system.
JNC Product Web Address:http://www.jnc-tec.com.tw/Main/List_Product.aspx?ProductType_ID=24
Specifications
Power |
110 VAC |
|
Display Color |
Full Color |
|
Display word |
Eight words in two lines |
|
Distance |
7.62mm |
|
Point |
32*128 point |
|
Physical |
Dimension (mm) |
1050 x 300 x 120 (W× H× D) |
Area (mm) |
975 x 244 |
|
Weight |
≦6kg |
|
Mounting |
Wall/ Panel mount |
|
Installation |
Indoor |
|
Case |
Material |
Aluminum Alloy |
Sensor |
||
(CO2) |
Operating Principle |
Non-dispersive infrared (NDIR) |
Sampling Response Time |
≦20 sec |
|
Range |
0~10,000ppms show to 9,999ppm |
|
Accuracy |
±30ppm ±2%Of Reading |
|
(Temp) |
Range |
-40~100℃ |
Accuracy |
±0.3℃ |
|
Repeatability |
±0.1℃ |
|
(RH) |
Range |
0~100% |
Accuracy |
±3% |
|
Repeatability |
±0.1% |
|
Response Time |
≦60sec. It should estimate the area of environment to balance time |
|
Power |
24VDC |
|
Environment |
Operating temperature |
-20~60℃ / 0 ~ 95%RH Non-condensing |
Storage temperature |
-30~70℃ |
|
Control Output |
Control point |
3 channel of 4-20mA (PID control) |
Relay contact capacity |
90~250VAC≧1A |
|
Communication |
Ethernet Interface |
RJ-45 with Ethernet Web Server、Protocol Modbus TCP |
Character String Interface |
RS-232/485 Protocol Modbus RTU |
|
Analog Output |
Output channel |
3 channels |
Current signal |
4-20mA (Setting with AO、PID or output control) |
|
Analog Input |
Input channel |
AIx3 channel (Provide 24VDC, collect data module,connect with JNC IAQ LED display monitoring system or anther graphic control system) |
Input signal |
4-20mA/ 0-5V |
|
Physical |
Dimension (mm) |
220 x 191.6 x 41.6(HxWxD) |
Weight |
1kg |
|
Case |
Material |
Stainless steel |